Breaker Panels
(Difference between revisions)
m (Updated circuit descriptions) |
(Noted additional plug.) |
||
| (16 intermediate revisions by 3 users not shown) | |||
| Line 1: | Line 1: | ||
| − | '''Office Subpanel on South Wall of Shop Area'''< | + | '''Office Subpanel on South Wall of Shop Area''' |
| − | (Service from 100A breaker above main disconnect, next to water heater) | + | |
| + | <blockquote style="background-color: lightgrey; border: solid thin grey; float: right; padding: 10px">{{QRcodeForThisPage}}</blockquote> | ||
| + | |||
| + | (Service from 100A breaker above main disconnect, next to water heater) | ||
| + | |||
(Federal Pacific, use NA-NI or NC-NI breakers) | (Federal Pacific, use NA-NI or NC-NI breakers) | ||
| Line 14: | Line 18: | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | | + | | E-room east bench plugs, west hallway plug, men's room plug |
| Sheathed cable into joist above office | | Sheathed cable into joist above office | ||
|- | |- | ||
| Line 20: | Line 24: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Crafts room east and south wall plugs, hallway plug between kitchen and bathroom, kitchen plugs on south wall but not on light switch |
| Sheathed cable into joist above office | | Sheathed cable into joist above office | ||
|- | |- | ||
| Line 26: | Line 30: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Plugs on pillar between south woodshop and large CNC area, lower plug on pillar north of tree house |
| − | | Through pipe in floor | + | | Through pipe in floor past Tree House |
|- | |- | ||
| 3 | | 3 | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | | + | | Hallway emergency exit light, hallway light inside front door, kitchen lights and plug on light switch, crafts room light |
| Sheathed cable into joist above office | | Sheathed cable into joist above office | ||
|- | |- | ||
| Line 38: | Line 42: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Tree House | + | | Tree House plug on southeast corner pillar (bell is connected), three plugs on horizontal beam on west side of Tree House |
| Through pipe in floor | | Through pipe in floor | ||
|- | |- | ||
| Line 44: | Line 48: | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | | + | | Fab room lights, e-room lights, e-room west bench plugs and west wall plug, bathroom lights and plug, men's room light |
| Sheathed cable into joist above office | | Sheathed cable into joist above office | ||
|- | |- | ||
| Line 50: | Line 54: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Bathroom | + | | Bathroom heat/fan |
| Sheathed cable into joist above office | | Sheathed cable into joist above office | ||
|- | |- | ||
| Line 68: | Line 72: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | IT shelf over front door, east shop ceiling fans, lights at main door, emergency exit lights at main door, kitchen plugs on north and east walls |
| − | + | | Conduit into office wall left of breaker panel | |
|- | |- | ||
| 11 | | 11 | ||
| Line 80: | Line 84: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Shop plugs east wall | + | | Shop plugs on east wall (welding shop, tool crib) |
| − | | Through pipe in floor | + | | Through pipe in floor |
|- | |- | ||
| 13 | | 13 | ||
| Line 93: | Line 97: | ||
| 40 | | 40 | ||
| Rooftop AC and heat | | Rooftop AC and heat | ||
| − | | To east loft, | + | | To east loft junction box, then to roof |
|- | |- | ||
| 15 | | 15 | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | | + | | Commons tables drop cords |
| To near-east junction box | | To near-east junction box | ||
|- | |- | ||
| Line 110: | Line 114: | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | | + | | Tool crib drop cord |
| To mid-east junction box | | To mid-east junction box | ||
|- | |- | ||
| Line 122: | Line 126: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Unknown |
| − | | To west loft ( | + | | To west loft/attic (lower knockout) |
|- | |- | ||
| 22a | | 22a | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | |||
| IT server rack power | | IT server rack power | ||
| + | | Plug left of breaker panel | ||
|- | |- | ||
| 22b | | 22b | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Not used |
| − | | To east loft | + | | To east loft junction boxes |
|- | |- | ||
| 23a | | 23a | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Unknown |
| − | | To west loft ( | + | | To west loft/attic (lower knockout) |
|- | |- | ||
| 23b | | 23b | ||
| Line 152: | Line 156: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Hallway lights (except light inside front door) |
| − | | To west loft ( | + | | To west loft (upper knockout) |
|} | |} | ||
| Line 178: | Line 182: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Shop plug next to Utilatub, switch to SW roof vent |
| | | | ||
|- | |- | ||
| Line 184: | Line 188: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | West shop ceiling fan, shop plug under west loft, fab lab plugs |
| | | | ||
|- | |- | ||
| Line 190: | Line 194: | ||
| N/A | | N/A | ||
| 15 | | 15 | ||
| − | | Rear shop lights and overhead power cord near utilitub | + | | Rear shop lights and overhead power cord near utilitub, plug on pillar near First Aid kit |
| No light switch | | No light switch | ||
|- | |- | ||
| Line 202: | Line 206: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | West shop emergency lights, west shop night lights |
| | | | ||
|- | |- | ||
| Line 208: | Line 212: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | West shop lights | + | | West shop lights, Tree House lights |
| No light switch | | No light switch | ||
|- | |- | ||
| Line 214: | Line 218: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | South shop wall plug next to broom rack |
| | | | ||
|- | |- | ||
| Line 220: | Line 224: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | West shop lights | + | | West shop lights, Tree House lights |
| No light switch | | No light switch | ||
|- | |- | ||
| Line 270: | Line 274: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Shop plugs on west wall behind sheet-goods and user storage areas |
| | | | ||
|- | |- | ||
| Line 276: | Line 280: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Unknown |
| | | | ||
|- | |- | ||
| Line 282: | Line 286: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Plugs on north wall, metalshop drop cord | + | | Plugs on north wall in western end of metal shop, metalshop drop cord |
| − | | | + | | Through handy box over woodshop/metalshop doorway |
|- | |- | ||
| 5b | | 5b | ||
| Line 294: | Line 298: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | West shop wall, six southernmost plugs |
| − | | | + | | |
|- | |- | ||
| 7 | | 7 | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Wood shop plugs on north wall and plug next to breaker panel. |
| | | | ||
|- | |- | ||
| Line 306: | Line 310: | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | | + | | Plug near surface grinder, metal shop lights |
| − | | | + | | Through handy box over woodshop/metalshop doorway |
|- | |- | ||
| 8b | | 8b | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Plugs on | + | | Plugs on north wall in eastern end of metal shop |
| − | | | + | | Conduit along north wall in loft |
|- | |- | ||
| 9 | | 9 | ||
| Line 325: | Line 329: | ||
| 20 | | 20 | ||
| Roof exhaust next to beam | | Roof exhaust next to beam | ||
| − | | | + | | Through handy box over woodshop/metalshop doorway |
|- | |- | ||
| 12 | | 12 | ||
| N/A | | N/A | ||
| 20 | | 20 | ||
| − | | Plugs | + | | Plugs for drill press and tool grinders, plugs under north wall clock |
| − | + | | Through handy box over woodshop/metalshop doorway | |
|} | |} | ||
<br> | <br> | ||
Revision as of 22:16, 10 January 2013
Office Subpanel on South Wall of Shop Area
(Service from 100A breaker above main disconnect, next to water heater)
(Federal Pacific, use NA-NI or NC-NI breakers)
| Location | Second Pole | Amperes | Description | Notes |
|---|---|---|---|---|
| 1a | N/A | 15 | E-room east bench plugs, west hallway plug, men's room plug | Sheathed cable into joist above office |
| 1b | N/A | 20 | Crafts room east and south wall plugs, hallway plug between kitchen and bathroom, kitchen plugs on south wall but not on light switch | Sheathed cable into joist above office |
| 2 | N/A | 20 | Plugs on pillar between south woodshop and large CNC area, lower plug on pillar north of tree house | Through pipe in floor past Tree House |
| 3 | N/A | 15 | Hallway emergency exit light, hallway light inside front door, kitchen lights and plug on light switch, crafts room light | Sheathed cable into joist above office |
| 4 | N/A | 20 | Tree House plug on southeast corner pillar (bell is connected), three plugs on horizontal beam on west side of Tree House | Through pipe in floor |
| 5 | N/A | 15 | Fab room lights, e-room lights, e-room west bench plugs and west wall plug, bathroom lights and plug, men's room light | Sheathed cable into joist above office |
| 6,8 | N/A | 20 | Bathroom heat/fan | Sheathed cable into joist above office |
| 7 | N/A | 15 | Shop lights (mid-east) | Leftmost of two switches left of breaker panel, to mid-east junction box |
| 9 | N/A | 15 | Shop lights over commons tables (near-east) | Lower switch left of breaker panel, to near-east junction box |
| 10 | N/A | 20 | IT shelf over front door, east shop ceiling fans, lights at main door, emergency exit lights at main door, kitchen plugs on north and east walls | Conduit into office wall left of breaker panel |
| 11 | N/A | 15 | Shop lights (far-east) | Rightmost of two switches left of breaker panel, to mid-east junction box |
| 12 | N/A | 20 | Shop plugs on east wall (welding shop, tool crib) | Through pipe in floor |
| 13 | N/A | 15 | North shop furnaces | To near-east junction box |
| 14, 16 | 18, 20 | 40 | Rooftop AC and heat | To east loft junction box, then to roof |
| 15 | N/A | 15 | Commons tables drop cords | To near-east junction box |
| 17 | N/A | 15 | Theater spotlights (south outlet) | To near-east junction box |
| 19 | N/A | 15 | Tool crib drop cord | To mid-east junction box |
| 21a | N/A | 15 | South-east shop furnace | To mid-east junction box |
| 21b | N/A | 20 | Unknown | To west loft/attic (lower knockout) |
| 22a | N/A | 15 | IT server rack power | Plug left of breaker panel |
| 22b | N/A | 20 | Not used | To east loft junction boxes |
| 23a | N/A | 20 | Unknown | To west loft/attic (lower knockout) |
| 23b | N/A | 20 | Theater spotlights (north outlet) | To near-east junction box |
| 24 | N/A | 20 | Hallway lights (except light inside front door) | To west loft (upper knockout) |
Panel in SW Corner of Shop Area
(Pushmatic Electri-Center)
| Location | Second Pole | Amperes | Description | Notes |
|---|---|---|---|---|
| 1 | 2 | 100 | Main | |
| 3 | N/A | 20 | Shop plug next to Utilatub, switch to SW roof vent | |
| 4 | N/A | 20 | West shop ceiling fan, shop plug under west loft, fab lab plugs | |
| 5 | N/A | 15 | Rear shop lights and overhead power cord near utilitub, plug on pillar near First Aid kit | No light switch |
| 6 | N/A | 20 | Not used | |
| 7 | N/A | 20 | West shop emergency lights, west shop night lights | |
| 8 | N/A | 20 | West shop lights, Tree House lights | No light switch |
| 9 | N/A | 20 | South shop wall plug next to broom rack | |
| 10 | N/A | 20 | West shop lights, Tree House lights | No light switch |
| 11 | N/A | N/A | Spare | No breaker installed |
| 12 | N/A | N/A | Spare | No breaker installed |
| 13 | 14 | 60 | Subpanel in rear shop |
Subpanel in NW Corner of Shop Area
(Resembles Pushmatic Electri-Center)
| Location | Second Pole | Amperes | Description | Notes |
|---|---|---|---|---|
| 1 | N/A | N/A | Spare | No breaker installed |
| 2 | N/A | N/A | Spare | No breaker installed |
| 3 | N/A | 20 | Shop plugs on west wall behind sheet-goods and user storage areas | |
| 4 | N/A | 20 | Unknown | |
| 5a | N/A | 20 | Plugs on north wall in western end of metal shop, metalshop drop cord | Through handy box over woodshop/metalshop doorway |
| 5b | N/A | 20 | Plugs on east wall | Breaker suspected bad, load moved to 7 |
| 6 | N/A | 20 | West shop wall, six southernmost plugs | |
| 7 | N/A | 20 | Wood shop plugs on north wall and plug next to breaker panel. | |
| 8a | N/A | 20 | Plug near surface grinder, metal shop lights | Through handy box over woodshop/metalshop doorway |
| 8b | N/A | 20 | Plugs on north wall in eastern end of metal shop | Conduit along north wall in loft |
| 9 | 10 | 20 | Roof exhaust fans | |
| 11 | N/A | 20 | Roof exhaust next to beam | Through handy box over woodshop/metalshop doorway |
| 12 | N/A | 20 | Plugs for drill press and tool grinders, plugs under north wall clock | Through handy box over woodshop/metalshop doorway |